Short description
| I/O module | X20 4-channel analog input module for vibration measurement of condition monitoring tasks |
General information
| Insulation voltage between channel and bus | 500 Veff |
| Nominal voltage | 24 VDC ±20% |
| B&R ID code | 0xF1C5 |
| Status indicators | Run, error, vibration inputs 1 to 4 |
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software |
| Power consumption | |
| Bus | 0.01 W |
| Internal I/O | 1.5 W |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
Analog inputs
| Quantity | 4 |
| Input type | IEPE sensor: Acceleration |
| Digital converter resolution | 24-bit |
| Open-circuit detection | |
| Per channel | Less than 8 V or greater than 14 V for more than 4 s |
| Permissible input signal | ±10 VAC |
| Conversion procedure | Sigma-delta |
| Type | Vibration input |
| Sampling frequency | Configurable from 200 Hz to 50 kHz |
| Input high pass cutoff frequency | 34 mHz |
| Input low pass cutoff frequency | 23 kHz |
| Sensor power supply | IEPE, 5 mA constant current source (4.9 - 5.5 mA), can be switched off for each channel |
Electrical properties
| Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 55°C |
| Derating | See section "Derating". |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note |
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5+0.2 mm |
Materiálové číslo:
X20CM4800XPopis:
- 4-channel vibration measurement module
- IEPE power supply
- Sampling rate of 200 to 50000 samples/second
- Separate Flatstream for each channel
This analog vibration measurement module can be operated with a configurable sampling rate of 200 to 50000 samples/second. The module has 4 input channels, which are transmitted with configurable 16-, 24- or 32-bit data resolution. Data is transferred for each channel via a separate Flatstream.
Povinné příslušenství
Bus modules
| X20BM11 | X20 bus module, 24 VDC keyed, internal I/O power supply connected through |
Terminal blocks
| X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Volitelné příslušenství
Sensor cable
| 0ACC0020.01-1 | Cable for accelerometer, length 2 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
| 0ACC0050.01-1 | Cable for accelerometer, length 5 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
| 0ACC0100.01-1 | Cable for accelerometer, length 10 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
| 0ACC0150.01-1 | Cable for accelerometer, length 15 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
| 0ACC0200.01-1 | Cable for accelerometer, length 20 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
| 0ACC0500.01-1 | Cable for accelerometer, length 50 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
| 0ACC1000.01-1 | Cable for accelerometer, length 100 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed |
Sensors
| 0ACS100A.00-1 | Accelerometer, nominal sensitivity 100 mV/g, top exit |
| 0ACS100A.90-1 | Accelerometer, nominal sensitivity 100 mV/g, side exit |
| 0ACS100A.90-2 | Accelerometer, nominal sensitivity 100 mV/g, output on side external hexagon |
| Automation Studio HW Upgrades | Verze (datum) | Ke stažení |
|---|---|---|
| V4.0 HW Upgrade (X20CM4800X) | EXE / 2 MB | |
| V4.1 HW Upgrade (X20CM4800X) | EXE / 2 MB | |
| V4.3 HW Upgrade (X20CM4800X) | EXE / 2 MB |
| Dokumentace | Verze (datum) | Ke stažení |
|---|---|---|
| Data sheet X20CM4800X | PDF / 1 MB | |
| X20 System User´s Manual | PDF / 45 MB |
| E-CAD (Electro or EPLAN Templates) | Verze (datum) | Ke stažení |
|---|---|---|
| Makro-/Artikeldaten 4.0.1 (X20CM4800X) | EXE / 582 KB | |
| X20 EPLAN P8 from V2.4 | EXE / 160 MB |
| M-CAD (Mechan. Templates) | Verze (datum) | Ke stažení |
|---|---|---|
| 3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
| 3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
| Dimensions PDF X20 Electronic module | PDF / 3 KB |