Short description
| Communication module | 1x RS232 |
General information
| B&R ID code | 0x1F27 |
| Status indicators | Module status, data transfer |
| Diagnostics | |
| Module status | Yes, using LED status indicator |
| Data transfer | Yes, using LED status indicator |
| Power consumption | 0.35 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL |
cULus E115267 Industrial control equipment |
| HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| KC | Yes |
Interfaces
| Interface IF1 | |
| Signal | RS232 |
| Variant | 9-pin male DSUB connector |
| Max. distance | 900 m |
| Transfer rate | Max. 115.2 kbit/s |
| Network-capable | No |
| FIFO buffer | 16 bytes in the transmit and receive directions |
| Handshake lines | RTS, CTS |
| Controller | UART type 16C550 compatible |
| Data formats | |
| Data bits | 5 to 8 |
| Parity | Yes / No / Even / Odd |
| Stop bits | 1 or 2 |
Electrical properties
| Electrical isolation | PLC isolated from RS232 (IF1) |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Slot | In the X20 PLC |
Número de material:
X20IF1020Descripción:
- The RS232 interface can be configured as an online interface
The interface module is used for application-specific expansion of the X20 controllers. It is equipped with an RS232 interface.
| Actualizaciones de hardware de Automation Studio | Versión (fecha) | Descargar |
|---|---|---|
| V2.7 HW Upgrade (X20IF1020) | EXE / 481 KB | |
| V2.7 HW Upgrade (X20IF1020) | EXE / 998 KB | |
| V3.0 HW Upgrade (X20IF1020) | EXE / 481 KB | |
| V3.0 HW Upgrade (X20IF1020) | EXE / 1 MB | |
| V4.0 HW Upgrade (X20IF1020) | EXE / 769 KB |
| Documentación | Versión (fecha) | Descargar |
|---|---|---|
| Data sheet X20IF1020 | PDF / 3 MB | |
| X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
| X20 System User´s Manual | PDF / 45 MB |
| E-CAD (plantillas Electro o EPLAN) | Versión (fecha) | Descargar |
|---|---|---|
| X20 EPLAN P8 from V2.4 | EXE / 160 MB |
| M-CAD (plantillas mecánicas) | Versión (fecha) | Descargar |
|---|---|---|
| 3D File DXF/STEP X20 Interface module X20IF1020, 1030 | ZIP / 1 MB |