DWL@DWL10000831886

Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.5.0.0 * 05/09/2025 4 Mo EXE AS6_HW_X20CM0985-02.exe
Description V6.0 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02

Version 1.5.0.0:

ID: TDYD-9281
Support new HW variant 2
UL6200 Certification
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\62501_1.fw(106), 1\62501_2.fw(106)

Version 1.4.3.0:

ID: 783310
Bug fix by splitting the data point ConfigOutput11_12 into ConfigOutput11 and ConfigOutput12
If ConfigOutput12 has a negative value, it will be overwritten in the initscript. By separating ConfigOutput11_12 into ConfigOutput11 and ConfigOutput12,this is prevented and all values ​​are adopted correctly.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(106)

Version 1.4.1.0:

ID: 721730
Value area extension for unbalanced load constant current asymmetry (K2).
A range of values ​​from 8 to 35 (0.08 to 0.35) is possible
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\62501_1.fw(106)

Version 1.4.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.3.0.0:

ID: 688200
Configuration parameter implemented to deactivate the evaluation of the current inputs if the generator voltages are missing
This prevents a noise at the current inputs being evaluated and leading to incorrect measured values, e.g. when the generator is not connected
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID:688210
Frequency measurement improved
Plausibility check is more robust against saddle-shaped signals in the areaof the zero crossing.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688215
Problem at startup of the X2X fixed
X2X telegrams are no longer forwarded too early to subsequent X2X slaves during the startup phase. Thus, it is no longer possible for a mismatched FW to be loaded to the subsequent X2X slave.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688220
Uneven load monitoring adapted for high unbalanced load currents
With unbalanced load currents above 4 times the nominal current, afault is no longer immediately output
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688225
additional continuous current tripping characteristics
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 690330
Module documentation revised
Data sheet V 1.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(105)

Version 1.2.0.0:

ID: 666915
Adaptations for Automation Studio 4.8
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 674335
Units adapted for display in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.1.0.0:

ID: 646225
If the "Over- and undervoltages check method" is configured to "Line voltages" or "Phase and line voltages", the "Over voltage of one phase" configuration is incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using thisupgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)