Short description
| I/O module | IO-Link master with 8 IO-Link interfaces |
| Interfaces | 1x X2X Link / X2X+ |
General information
| B&R ID code | 0x30AE |
| Status indicators | IO-Link, operating state, module status |
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software |
| IO-Link operating state | Yes, using LED status indicator and software |
| C/Q status | Yes, using LED status indicator and software |
| Cable specification | |
| Cable type | 4-pin standard sensor cable, unshielded |
| Cable length | Max. 20 m |
| Line capacitance | Max. 3 nF |
| Loop resistance | Max. 6 Ω |
| Power consumption | |
| Bus | 0.6 W |
| Internal I/O | 1 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
Sensor/Actuator power supply
| Voltage | I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 0.5 A | Max. 0.3 V |
| Power consumption | Max. 12 W per IO-Link interface |
| Short-circuit proof | Yes |
| Overload protection | |
| Switch-off delay | Configurable using software |
| Switch-off duration | Configurable using software |
IO-Link in master mode
| Transfer rates | |
| COM1 | 4.8 kbaud |
| COM2 | 38.4 kbaud |
| COM3 | 230.4 kbaud |
| Limit values for COM3 | |
| Max. connection capacity | 22 nF (cable + IO-Link device) |
| Max. load | 96 Ω / 250 mA |
| Data format | 1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit |
| Bus level | 24 VDC (active), 0 VDC (resting voltage) |
IO-Link in master mode or in SIO mode "digital output"
| Variant | Bipolar, positive and negative switching |
| Peak short-circuit current | <1.3 A |
| Residual voltage | <0.7 VDC at nominal current 0.25 A |
| Switching voltage | I/O power supply minus voltage drop for short-circuit protection and semiconductor switch |
| Voltage drop on semiconductor switch | Max. 0.5 VDC at 0.25 A |
| Switching frequency |
Typ. 25 kHz 300 kHz in IO-Link master mode |
| Switching delay | |
| 0 → 1 | <10 µs |
| 1 → 0 | <10 µs |
| Switch-on in the event of overload shutdown or short-circuit shutdown | Configurable with software |
| Insulation voltage between IO-Link and bus | 860 Veff |
IO-Link in SIO mode "Digital output"
IO-Link in SIO mode "digital input"
| Nominal voltage | 24 VDC |
| Input characteristics per EN 61131-2 | Type 1 |
| Input filter | |
| Hardware | 300 ns |
| Software | - |
| Input circuit | Sink |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Typ. 4 mA |
| Input resistance | Typ. 6 kΩ |
| Switching threshold | |
| Low | <5 VDC |
| High | >15 VDC |
| Insulation voltage between IO-Link and bus | 860 Veff |
Electrical properties
| Electrical isolation |
Bus isolated from IO-Link IO-Link not isolated from IO-Link |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Maximum | 4000 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order terminal blocks separately (see section "Order data"). |
| Dimensions | |
| Width (pitch) | 27.5 +0.2 mm |
| Height | 124 mm |
| Depth | 92 mm |
Numero materiale:
X20DS838ADescrizione:
- 8 IO-Link channels (port class A)
- Each IO-Link channel can be configured as a digital input or output (SIO mode)
- Additional digital input per IO-Link connection
- 24 VDC and GND for sensor/actuator power supply
- NetTime timestamps: IO-Link data
The module is an IO-Link master that allows intelligent sensors and actuators to be connected per the IO-Link standard. The module can operate up to 8 IO-Link devices. The significant increase in cyclic data with this product variant enables optimal operation of IO-Link devices. Flatstream communication is now only used in exceptional cases. All IO-Link channels can also be operated in SIO mode and thus used as digital inputs or outputs. The module is also equipped with 8 additional digital inputs that can be used independently of the configuration of the IO-Link channels.
Accessori obbligatori
| Aggiornamenti HW di Automation Studio | Versione (data) | Download |
|---|---|---|
| V4.12 HW Upgrade (X20DS838A) | EXE / 3 MB | |
| V6.0 HW Upgrade (X20DS838A) | EXE / 3 MB |
| Certificati | Versione (data) | Download |
|---|---|---|
| EU Data Act - X20 IO - Connected Product Information Notice | PDF / 92 KB | |
| EU Declaration of conformity PLC X20 | PDF / 169 KB | |
| UK Declaration PLC X20 | PDF / 151 KB |
| Documentazione | Versione (data) | Download |
|---|---|---|
| Data sheet X20DS838A | PDF / 3 MB | |
| X20 System User´s Manual | PDF / 45 MB |
| E-CAD (Electro o EPLAN Template) | Versione (data) | Download |
|---|---|---|
| Makro-/Artikeldaten 4.0.5 (X20DS838A) | EXE / 2 MB |
| M-CAD (Mechan. Template) | Versione (data) | Download |
|---|---|---|
| 3D files DXF/STEP X20DS838A | ZIP / 5 MB |