Short description
| Bus module | X2X+ power supply bus module, not mechanically keyed, internal I/O power supply interrupted to the left |
General information
| B&R ID code | 0xF377 |
| Power consumption | |
| Bus | 0.45 W |
| Internal I/O | - |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| UL |
cULus E115267 Industrial control equipment |
I/O power supply
| Nominal voltage | 24 VDC |
| Permissible contact load | 10 A |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 50°C |
| Vertical mounting orientation | -25 to 45°C |
| Derating | - |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Pitch | 12.5+0.2 mm |
Materiaalnummer:
X20BM01XOmschrijving:
- Basis for all power supply modules
- For creating potential groups
- The internal I/O power supply is interrupted to the left.
The X2X+ bus module is the base for all power supply modules.
| Automation Studio HW Upgrades | Versie (Datum) | Download |
|---|---|---|
| V4.7 HW Upgrade (X20BM01X) | EXE / 1 MB | |
| V6.0 HW Upgrade (X20BM01X) | EXE / 1 MB |
| Documentatie | Versie (Datum) | Download |
|---|---|---|
| Data sheet X20BM01X | PDF / 215 KB | |
| X20 System User´s Manual | PDF / 45 MB |
| E-CAD (Electro of EPLAN Templates) | Versie (Datum) | Download |
|---|---|---|
| X20 EPLAN P8 from V2.4 | EXE / 160 MB |